JV Series – JVR-CPA-315-2/4-3
Description
The JV Series of JetVent axial fans have been designed
to provide effective ventilation in most spaces that contain harmful vehicle exhaust pollutants. They can be supplied
for uni-directional or truly reversible air flow and are available
in 2 sizes, 315mm and 400mm diameter. Units approved
to AS4429:1999 for smoke exhaust are also available.
Features
- Available with single (high) or 2 speed (high/low) motor.
- Integral aerodynamically designed silencers provide quiet operation.
- Bell mouth inlet and outlet optimises performance.
- Units can be speed controlled using Variable Speed Drives.
- Can be supplied for uni-directional or truly reversible air flow.
- Fitted with a high performance aerofoil impeller.
- Durable galvanised steel housing with light grey powder coated finish as standard.
- Integral mounting feet allows unit to be easily mounted to ceiling.
- Electrical isolator fitted on ambient temperature units.
Construction
Galvanised steel housing with integral aerodynamically designed silencers. Light grey powder coated finish is standard. Axial flow aerofoil impellers manufactured from aluminium.
Motors
Type - squirrel cage induction motor.
Electricity supply - 415V, three-phase, 50Hz.
Bearings - sealed-for-life, ball.
Single or 2-speed as nominated.
Speed controllable using frequency inverters.
Standard motors are suitable for ambient conditions up to 40°C.
Units for high temperature conditions, such as smoke-control, are available.
Internal Thermal Protection
Thermisters can be provided on all motors except where Standards prohibit their use.
Testing
Thermistors performance based on tests to BS848 Part 10,1999:
"Fans for general purpose - Performance testing of jet fans".
Noise data based on tests to BS848:Part 2, 1985.
High temperature tests to AS4429:1999.
Special NoteJet fans should be treated as an Alternative Solution within the
National Construction Code (NCC)(formerly the BCA) from a fire
and smoke control perspective (in addition to the ventilation
requirements). Therefore the fire engineer on the project would
need to add the car park ventilation design into their fire
engineering report for the project and ensure that they meet the
relevant BCA performance clauses. For more information please
refer to the JetVent “Practical Guide for Selection and
Application”
Smoke-Spill Applications
Smoke-spill models have been fully tested to meet the air performance and high temperature requirements of Standards AS/NZS1668.1:1998 and AS4429:1999.
In the case of a fire occurring, smoke-spill models will stop
operating for a predetermined time to allow occupants to
escape the building. After this time the fan will commence
operation again.
Control Systems
There are two types of analogue control systems used with the JetVent JV Series:
- Two speed system using relays to drive contactors connected to the fans
- Variable speed system using 0 to 10 Vdc outputs to proportionally drive VSDs
Suggested Specification
The high velocity axial jet fans shall be of the JetVent JV Series as designed and manufactured by Fantech Pty Ltd. and be of the model number shown. The housing shall be of galvanised steel with a light grey powder coated finish as standard. They shall incorporate aluminium axial impellers of aerofoil design and aerodynamically engineered silencers. They shall be single
or 2-speed as nominated.
Performance data shall be based on tests to BS848:Part 10,1999 for thrust and BS848:Part 2, 1985 for noise. Units
for smoke-spill applications shall be tested to AS4429:1999.
Technical Data - JVR-CPA-315-2/4-3
Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] |
---|
48 | 61 | 0.8 | 1.9 | 40 | 62 |
Sound Data
Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K |
---|
Inlet | 73 | 82 | 87 | 79 | 74 | 69 | 67 | 64 |
Dimensions
A | B | C | D | E | F | G | H |
---|
1808 | 142 | 336 | 417 | 25 | 13 | 367 | 360 |
*All dimensions in mm, unless otherwise stated
Ancillaries