Products  Fans  By Mounting Type  Heritage Series – CHD454
Download Catalogue  Autocad  Print Friendly Version

Heritage Series – CHD454

Heritage Series

Performance Curve - CHD454

Description

The Heritage Series of vertical exhaust roof units has been designed for use in ducted exhaust applications. It features a high performance centrifugal fan and removable windband which makes cleaning and maintenance easy.
There are 8 sizes in the series extending from 315 to 710mm diameter.
Features
  • Durable galvanised steel construction with coated finish.
  • Designed to handle clean air, grease laden air, toxic noxious and explosive gases as well as handling air at elevated temperatures.
  • Motor is mounted out of the airstream.
  • Motors to suit hazardous conditions can be fitted to some models.
  • Special finishes, such as epoxy coating can be supplied.
  • Available in a range of speeds to suit specific applications.
  • Windband can be easily removed to allow easy access for cleaning and maintenance.
  • Can be mounted at angles up to 15°.
  • Construction
    Cowls are of galvanised steel with coated finish.
    Impellers are a backward-curved centrifugal design.
    Windband is fitted with quick-release toggle clamps to facilitate cleaning and maintenance.
    Stainless steel construction is an optional extra.
    Motors
    Type - standard TEFC squirrel cage induction motors.
    Electricity supply - single or three-phase to suit a wide range of voltages and frequencies.
    Bearings - sealed-for-life, ball.
    Three phase motors speed-controllable using variable speed drives.
    Multi-speed motors can be supplied.
    Motors to meet Ex e, Ex nA and Ex tD
    Standards can be fitted to some models.
    Internal Thermal Protection
    Thermistors can be fitted on request
    Testing
    Air flow to ISO 5801: 2007
    Noise tests to ISO3744: 2010

    Suggested Specification

    The Heritage Series of vertical exhaust centrifugal roof ventilators shall be as designed and manufactured by Fantech Pty Ltd.
    The cowl shall be of coated galvanised steel unless specified otherwise. Impellers shall be backward-curved centrifugal design and driven by standard TEFC motors unless specified otherwise.
    The windband shall incorporate quick-release toggle clamps to provide easy access for cleaning and maintenance.
    All models shall be fully tested as a complete assembled unit to ISO5801: 2007 for air flow and to ISO3744: 2010 for noise.

    Technical Data - CHD454

    Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
    24580.751.794049

    Sound Data

    Type631252505001K2K4K8K
    Inlet8583787569707066

    Dimensions

    ABCDEF
    62072060900540790

    *All dimensions in mm, unless otherwise stated

    Wiring Diagram


    Diagram shown is for single-speed only.
    For 2-speed and special motors, contact Fantech for details.

    Ancillaries