Products  Fans  By Mounting Type  JV Series – JVU-CPA-400-2/4-3
Download Brochure  Autocad  Print Friendly Version

JV Series – JVU-CPA-400-2/4-3

JV Series

Description

The JV Series of JetVent axial fans have been designed to provide effective ventilation in most spaces that contain harmful vehicle exhaust pollutants. They can be supplied for uni-directional or truly reversible air flow and are available in 2 sizes, 315mm and 400mm diameter. Units approved to AS4429:1999 for smoke exhaust are also available.
JV Series - JetVent Axial Jet Fans
Features
  • Available with single (high) or 2 speed (high/low) motor.
  • Integral aerodynamically designed silencers provide quiet operation.
  • Bell mouth inlet and outlet optimises performance.
  • Units can be speed controlled using Variable Speed Drives.
  • Can be supplied for uni-directional or truly reversible air flow.
  • Fitted with a high performance aerofoil impeller.
  • Durable galvanised steel housing with light grey powder coated finish as standard.
  • Integral mounting feet allows unit to be easily mounted to ceiling.
  • Electrical isolator fitted on ambient temperature units.
Construction
Galvanised steel housing with integral aerodynamically designed silencers. Light grey powder coated finish is standard. Axial flow aerofoil impellers manufactured from aluminium.
Motors
Type - squirrel cage induction motor.
Electricity supply - 415V, three-phase, 50Hz.
Bearings - sealed-for-life, ball.
Single or 2-speed as nominated.
Speed controllable using frequency inverters.
Standard motors are suitable for ambient conditions up to 40°C.
Units for high temperature conditions, such as smoke-control, are available.
Internal Thermal Protection
Thermisters can be provided on all motors except where Standards prohibit their use.
Testing
Thermistors performance based on tests to BS848 Part 10,1999:
"Fans for general purpose - Performance testing of jet fans".
Noise data based on tests to BS848:Part 2, 1985. High temperature tests to AS4429:1999.
Special Note
Jet fans should be treated as an Alternative Solution within the National Construction Code (NCC)(formerly the BCA) from a fire and smoke control perspective (in addition to the ventilation requirements). Therefore the fire engineer on the project would need to add the car park ventilation design into their fire engineering report for the project and ensure that they meet the relevant BCA performance clauses. For more information please refer to the JetVent “Practical Guide for Selection and Application”

Smoke-Spill Applications
Smoke-spill models have been fully tested to meet the air performance and high temperature requirements of Standards AS/NZS1668.1:1998 and AS4429:1999.

In the case of a fire occurring, smoke-spill models will stop operating for a predetermined time to allow occupants to escape the building. After this time the fan will commence operation again.

Control Systems
There are two types of analogue control systems used with the JetVent JV Series:

  • Two speed system using relays to drive contactors connected to the fans
  • Variable speed system using 0 to 10 Vdc outputs to proportionally drive VSDs

Suggested Specification

The high velocity axial jet fans shall be of the JetVent JV Series as designed and manufactured by Fantech Pty Ltd. and be of the model number shown. The housing shall be of galvanised steel with a light grey powder coated finish as standard. They shall incorporate aluminium axial impellers of aerofoil design and aerodynamically engineered silencers. They shall be single or 2-speed as nominated.

Performance data shall be based on tests to BS848:Part 10,1999 for thrust and BS848:Part 2, 1985 for noise. Units for smoke-spill applications shall be tested to AS4429:1999.

Technical Data - JVU-CPA-400-2/4-3

Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
48621.73.54071

Sound Data

Type631252505001K2K4K8K
Inlet8681887970697068

Dimensions

Ancillaries